Communication · wired

M-Bus for water and heat meters

The Meter-Bus is the standard in consumption metering for connecting many meters to a single line. This page shows how the H2O and DELTA III connect to M-Bus, what to consider at the planning stage and how the values reach the control system.

How it works

One master, two wires, many meters

M-BuswiredRS-485 · Modbus RTUwiredLoRaradio, 868 MHzEMU M-CenterM-Bus masterHelvatron H2OSecondary address 2401 0001DELTA IIISecondary address 2401 0002Helvatron H2OSecondary address 2401 0003about 40 V · 2 wiresSelection by secondary addressReply by current modulationModbus masterGateway or controllerHelvatron H2OAddress 1DELTA IIIAddress 2Helvatron H2OAddress 3120 Ω120 ΩA/B twisted + GNDRequest: address 2 · FC 03Response with CRC-16Applicatione.g. Joulio-Web, control systemNetwork serverGatewayGatewayHelvatron H2OLoRaDELTA IIILoRaUplink 868 MHzJoin via OTAARange depends on building and site
  1. M-Bus: one cable, many metersThe master supplies the two-wire line with about 40 V. All meters are connected in parallel; polarity does not matter.
  2. M-Bus: readingThe master selects a meter by its secondary address. Only that meter replies, by modulating its current draw.
  3. RS-485: line with terminationA twisted pair A/B runs as a line from device to device, with 120 Ω at both ends. RS-485 is the physical interface.
  4. Modbus RTU: request and responseThe protocol layer: the master polls a slave address (1–247) with a function code; the meter replies with a CRC-16 checksum.
  5. LoRa: radio to the gatewayThe meter sends short uplinks on 868 MHz. Every gateway in range receives them, with no cable to the metering point.
  6. LoRa: server and applicationGateways forward the data to the network server, which passes it on to the application. Range and transmission interval limit data volume and timeliness.
Simplified illustration. IDs and addresses are examples.

How is an M-Bus system structured?

An M-Bus master, for example a data logger, supplies a two-wire line. All meters are connected in parallel; polarity does not matter. Line, star and tree topologies are possible; rings should be avoided.

In the idle state, each meter draws a standard load of about 1.5 mA from the bus. The master must be able to supply the total of all loads. When a meter replies, it briefly increases its current draw, and the master detects this change.

Addressing

In addition to the primary address (1 to 250), every meter has a unique secondary address assigned at the factory. The master uses it to select a specific meter, with no need to assign addresses on site. Helvatron meters identify themselves with the manufacturer code HVT.

Bus power

The H2O can optionally be powered via the M-Bus. The DELTA III is available with M-Bus power and a backup battery. Without this option, both meters run on battery power and the M-Bus is used for communication only.

Planning notes

  • Add up the number of meters and their standard loads for the master
  • Choose cable length and cross-section according to the master manufacturer’s specifications
  • Typical baud rate 2400 Bd; a telegram takes well under a second
  • Document secondary addresses and meter locations during installation
  • Heat meters and water meters can run on the same bus

System design

From the M-Bus to the building management system

A typical set-up: a building’s meters are connected to an EMU M-Center, which reads the meters, stores the values and passes them on to higher-level systems.

H2O and DELTA IIIwith M-Bus interface, manufacturer code HVT
EMU M-CenterM-Bus master for up to 250 devices
Building automation, billing, Joulio-WebVisualisation and analysis

Step by step: commissioning the EMU M-Center with the H2O and DELTA III. Our sister company EMU covers M-Bus basics in detail, including bus load calculation, on emuag.com.

Versions

H2O and DELTA III with M-Bus

H2O with M-Bus

DN15 to DN500, part number suffix ABM, for example WABG.20C.ABM for DN20. Also available with wireless M-Bus (S1, T1 and OMS).

H2O part numbers

DELTA III with M-Bus

DN15 to DN1000, suffix ABM. Combined with RS-485 (ABMM) or LoRa (ABML) for two communication paths.

DELTA III part numbers

Questions about M-Bus

Do I need to observe polarity when connecting?

No. M-Bus is polarity-independent, so the two wires can be swapped.

How many meters can an EMU M-Center read?

Up to 250 M-Bus devices. Its two RS-485 interfaces add up to 64 Modbus devices.

Which manufacturer code do Helvatron meters use?

HVT. The master uses this code to recognise Helvatron devices when scanning the bus.